K. Connection of Customer Facilities RSP K-3
 
table of contents | back          k1 | k2 | k3 | k4       next
 

Metering Equipment, except as noted below, is installed on the low voltage side of the transformer. General Service and small industrial Customers are primary metered under any of the following circumstances:

  • Service entrance size exceeds 1200 amps.
  • The Customer requests that the transformer be placed indoors.
  • The Customer requires a voltage that is not an NB Power standard service voltage.

Large industrial Customers are normally metered at a primary voltage of 69 kV or above; if they are metered at a voltage below 69 kV, readings are adjusted for the associated transformation losses.

Metering
Equipment cont'd

 
Normally, NB Power installs a meter for each individual building of a Premises except as follows:

A group of adjacent buildings located on the same property served by one electric service is accepted by NB Power as one Customer for billing purposes if the buildings:

  • are owned by the Applicant;
    (and)
  • are used for a related purpose.

The meter may be installed at either a primary or secondary voltage level. The Customer must supply, install, own and maintain all primary and/or secondary facilities beyond the Delivery Point.

Specific applications of a maypole or primary voltage supply are specified in the following sections.

Secondary Voltage Supply/Maypole Service

The Delivery point is generally at a maypole on the Customer's property at a secondary voltage. The maypole, conductors from NB Power Facilities to the maypole, the anchor and Metering Equipment are NB Power Facilities. NB Power makes all connections at the maypole.

Service to
Multiple
Buildings
 
table of contents | back          k1 | k2 | k3 | k4 next
disclaimer | NB Power - RSP 1 January 1990

 
 
 
 
 
Advanced Search
  Customer Service Policies
  Media
  Tenders
  Careers
  Outage Information
  A. Introduction
  B. Definition of Terms
  C. Authority, Authorizations and Contracts
  D. Provision of Service
  E. Security Deposits
  F. Billing and Payments
  G. Services Available to Customers
  H. Extension of Facilities - Overhead
  I. Extension of Facilities - Underground
  J. Optional Facilities
  K. Connection of Customer Facilities
  L. Use of Service
  M. Disconnection of Service
  N. Rate Schedules and Rate Application Guidelines
  O. Fees and Charges
 
 
 
 
 
  © 2007 Énergie NB Power   |   Privacy Policy